IEC 类别
|
C1
|
|
C2
|
|
C3
|
|
D1
|
额定电压 UN
|
12 V DC
|
较大持续工作电压UC
|
15 V DC
|
额定电流
|
600 mA (56 °C)
|
UC时,有效工作电流IC
|
≤ 100 μA
|
残流IPE
|
≤ 1 μA
|
标称放电电流In (8/20) μs(线芯-线芯)
|
5 kA
|
标称放电电流In (8/20) μs(线芯-地)
|
5 kA
|
标称放电电流In (8/20) μs(线芯-信号接地)
|
5 kA
|
脉冲放电电流Iimp (10/350) μs(线芯-线芯)
|
0.5 kA
|
脉冲放电电流Iimp (10/350) μs(线芯-地)
|
0.5 kA
|
脉冲放电电流Iimp(10/350) μs(线-信号地)
|
0.5 kA
|
总放电电流Itotal (8/20) μs
|
10 kA
|
电压保护水平Up(线芯-线芯)
|
≤ 220 V (C1 - 1 kV/500 A)
|
|
≤ 350 V (C2 - 10 kV / 5 kA)
|
|
≤ 25 V (C3 - 25 A)
|
|
≤ 35 V (C3 - 100 A)
|
电压保护水平Up(线芯-地)
|
≤ 900 V (C1 - 1 kV/500 A)
|
|
≤ 1.05 kV (C2 - 10 kV / 5 kA)
|
|
≤ 1.3 kV (C3 - 25 A)
|
|
≤ 1.4 kV (C3 - 100 A)
|
电压保护水平Up(线-信号地)
|
≤ 750 V (C1 - 1 kV/500 A)
|
|
≤ 750 V (C2 - 10 kV / 5 kA)
|
|
≤ 700 V (C3 - 25 A)
|
|
≤ 750 V (C3 - 100 A)
|
电压防护等级Up静态(线芯-线芯)
|
≤ 30 V (C1 - 1 kV/500 A)
|
|
≤ 85 V (C2 - 10 kV / 5 kA)
|
电压防护等级Up静态(线芯-接地)
|
≤ 900 V (C1 - 1 kV/500 A)
|
|
≤ 1.05 kV (C2 - 10 kV / 5 kA)
|
电压保护水平Up静态(线-信号地)
|
≤ 750 V (C1 - 1 kV/500 A)
|
|
≤ 750 V (C2 - 10 kV / 5 kA)
|
响应时间tA(线芯-线芯)
|
≤ 1 ns
|
响应时间tA(线-信号地)
|
≤ 100 ns
|
响应时间tA(线芯-地)
|
≤ 100 ns
|
输入衰减aE,对称
|
典型值 0.3 dB (≤ 130 kHz / 150 Ω)
|
截止频率fg(3dB),150 Ω 对称系统
|
典型值 420 kHz
|
电容(线芯-线芯)
|
典型值 5.2 nF
|
每个路径的电阻
|
1.65 Ω ±20 %
|
电涌保护故障报警
|
带可视状态指示窗口
|
需要的较大备用保险丝
|
630 mA (FF)
|
电涌电流电阻(导线-导线)
|
C1 - 1 kV/500 A
|
|
C2 - 10 kV/5 kA
|
|
C3 - 100 A
|
电涌电流电阻(导线-接地)
|
C1 - 1 kV/500 A
|
|
C2 - 10 kV/5 kA
|
|
C3 - 100 A
|
|
D1 - 500 A
|
电涌电流承载能力(线-信号地)
|
C1 - 1 kV/500 A
|
|
C2 - 10 kV/5 kA
|
|
C3 - 100 A
|
|
D1 - 500 A
|
脉冲复位时间(导线-导线)
|
≤ 700 ms
|
脉冲复位时间(导线-接地)
|
≤ 30 ms
|
脉冲复位时间(线-信号地)
|
≤ 1500 ms
|